Prosecution Insights
Last updated: April 17, 2026
Application No. 17/853,974

HIGH-VOLTAGE TRIGGERED PULSECLOSER WITH ADAPTIVE CIRCUIT TESTING

Non-Final OA §102
Filed
Jun 30, 2022
Examiner
NGUYEN, DANNY
Art Unit
2838
Tech Center
2800 — Semiconductors & Electrical Systems
Assignee
S&C Electric Company
OA Round
1 (Non-Final)
90%
Grant Probability
Favorable
1-2
OA Rounds
2y 6m
To Grant
96%
With Interview

Examiner Intelligence

Grants 90% — above average
90%
Career Allow Rate
1207 granted / 1340 resolved
+22.1% vs TC avg
Moderate +6% lift
Without
With
+6.4%
Interview Lift
resolved cases with interview
Typical timeline
2y 6m
Avg Prosecution
31 currently pending
Career history
1371
Total Applications
across all art units

Statute-Specific Performance

§101
0.2%
-39.8% vs TC avg
§103
38.2%
-1.8% vs TC avg
§102
52.1%
+12.1% vs TC avg
§112
6.3%
-33.7% vs TC avg
Black line = Tech Center average estimate • Based on career data from 1340 resolved cases

Office Action

§102
DETAILED ACTION Notice of Pre-AIA or AIA Status The present application, filed on or after March 16, 2013, is being examined under the first inventor to file provisions of the AIA . Claim Rejections - 35 USC § 102 In the event the determination of the status of the application as subject to AIA 35 U.S.C. 102 and 103 (or as subject to pre-AIA 35 U.S.C. 102 and 103) is incorrect, any correction of the statutory basis (i.e., changing from AIA to pre-AIA ) for the rejection will not be considered a new ground of rejection if the prior art relied upon, and the rationale supporting the rejection, would be the same under either status. The following is a quotation of the appropriate paragraphs of 35 U.S.C. 102 that form the basis for the rejections under this section made in this Office action: A person shall be entitled to a patent unless – (a)(1) the claimed invention was patented, described in a printed publication, or in public use, on sale, or otherwise available to the public before the effective filing date of the claimed invention. 1. Claims 1, 3, 4, 6-8, 12-15, 18-20 are rejected under 35 U.S.C. 102 (a)(1) as being anticipated by Montenegro et al (USPN 2010/0296215). Regarding claim 1, Montenegro discloses a method (see figures 3-4) for maintaining electrical stability of a power system (a power system shown in 1) in response to a fault, the method comprising: detecting the fault (step 404, see par. 0028); opening a switch (such as a vacuum interrupter 1302, figure 13, to clear the fault (step 408); performing a first pulse test (such as a test pulse shown in figure 3, step 410) for a predetermined duration of time (e.g. about 0.5 second, see par. 0034) to determine if the fault is still present (see step 416); preventing a reclosing operation by the switch from occurring if the first pulse test indicates that the fault is still present (step 426, par. 0033); and allowing the reclosing operation (418) to occur if the first pulse test indicates that the fault is no longer present (e.g. see par. 0032). Regarding claims 3, 14, 17, Montenegro discloses wherein the predetermined duration of time is less than or equal 0.5 cycles (such as haft cycle pulses 208, 504, see figures 3, 5, par. 0031). Regarding claims 4, 15, Montenegro discloses further comprising performing subsequent pulse tests (see step 414) if the first pulse test is inclusive about the persistence of the fault (see par. 0033) , wherein preventing a reclosing (step 426) operation from occurring includes preventing the reclosing operation from occurring if any of the pulse tests indicates that the fault is still present (see par. 0033) and allowing the reclosing operation to occur includes allowing the reclosing operation (418) to occur if any of the pulse tests indicates that the fault is no longer present (e.g. see par. 0032). Regarding claims 6, 18, Montenegro discloses wherein the first pulse test is performed at a predetermined point-on-wave time (such as 208, 210). Regarding claims 7, 20, Montenegro discloses wherein the power system is a high-voltage transmission power system (see par. 0021, see figure 1). Regarding claims 8, 19, Montenegro discloses wherein the reclosing operation is performed by the switch (1302, see figure 13). Regarding claims 12, 13, 16, Montenegro discloses a system (10, see figures 1-2) for maintaining electrical stability of a power network in response to a fault, the system comprising: Sensors (a fault sensor of the circuit tester 130, see par. 0019) coupled to the power network (a network in figure 1) and to a controller (a controller of the circuit tester 130, see par. 0020) couple to the sensors, the sensors and controller operable to detect the fault (see par. 0019); an actuator (814) (an actuation mechanism of the circuit tester 130 shown in figure 8, see par. 0066) coupled to a switch (12), the actuator being operable in the presence of a fault to open the switch to clear the fault (see par. 0070); a first pulse tester (a circuit tester 130) coupled to the power network, the first pulse tester being operable to perform a pulse test of the power network for a predetermined duration of time (about 0.5 second) to determine if the fault is still present (such as see figure 3, steps 410, 416 par. 0034); the actuator (814) being configured to prevent a reclosing of the switch (the vacuum switch of the tester 130, see figures 8, and 13) where the first pulse test indicates that the fault is still present (see par. 0033, 0078); and the actuator being further configured to provide the reclosing operation where the first pulse test indicates that the fault is not present (see par. 0078). 2. Claims 1-20 are rejected under 35 U.S.C. 102 (a)(1) as being anticipated by Djogo et al (USPN 2020/0191855). Regarding claim 1, Djogo discloses a method (see figures 1-2, 8) for maintaining electrical stability of a power system (a power system 10 shown in 1) in response to a fault, the method comprising: detecting the fault (step 142, see par. 0044); opening a switch (such as a switch 12) to clear the fault (step 408, see par. 0008); performing a first pulse test (such as a test pulse generated from a triggering circuit 42, also step 148) for a predetermined duration of time (e.g. about 0.5 nanosecond, see par. 0039, 0045) to determine if the fault is still present (see step 416); preventing a reclosing operation (see step 156) from occurring if the first pulse test indicates that the fault is still present (par. 0048); and allowing the reclosing operation (step 154) to occur if the first pulse test indicates that the fault is no longer present (e.g. see par. 0047). Regarding claim 2, Djogo discloses wherein the first pulse test is performed by a triggered vacuum gap (TVG) device (36, see figure 4). Regarding claims 3, 10, 14, 17, Djogo discloses wherein the predetermined duration of time is less than or equal 0.5 cycles (e.g. see par. 0006). Regarding claim 4, Djogo discloses further comprising performing subsequent pulse tests (see step 158) if the first pulse test is inclusive about the persistence of the fault (see steps 148, 152) , wherein preventing a reclosing operation from occurring includes preventing the reclosing operation from occurring if any of the pulse tests indicates that the fault is still present (see par. 0048) and allowing the reclosing operation to occur includes allowing the reclosing operation to occur if any of the pulse tests indicates that the fault is no longer present (e.g. steps 146, 148, 152, and 154). Regarding claim 5, Djogo discloses wherein the first and subsequent pulse tests are performed by a triggered vacuum gap (TVG) device (42, 36). Regarding claims 6, 11, 18, Dojogo discloses wherein the first pulse test is performed at a predetermined point-on-wave time (see par. 0050). Regarding claims 7, 20, Djogo discloses wherein the power system is a high-voltage transmission power system ( see figure 1). Regarding claim 8, Djogo discloses wherein the reclosing operation is performed by the switch (12). Regarding claim 9, Djogo discloses a method (figure 8) for maintaining electrical stability of a high-voltage transmission power system (10, see figure 1) in response to a fault, the method comprising: detecting the fault (by step 142); opening a switch (a switch 12) to clear the fault; performing a first pulse test for a predetermined duration of time (such as 0.5 nanosecond) using a triggered vacuum gap (TVG) device (42, 36 and steps 148) to determine if the fault is still present (see par. 0039, 0045); performing subsequent pulse tests by the TVG device (by loop steps 148, 150, 152, 158) for the predetermined duration of time if the first pulse test is inclusive about the persistence of the fault; preventing a reclosing operation (step 156, see par. 0048) by the switch (12) from occurring if the pulse tests indicate that the fault is still present; and allowing the reclosing operation (step 154, par. 0047) to occur by the switch if the pulse tests indicate that the fault is no longer present. Regarding claims 12, 13, 16, 19, Dojogo discloses a system (10, see figures 1-2) for maintaining electrical stability of a power network in response to a fault, the system comprising: Sensors (28, 32) coupled to the power network and to a controller (34) couple to the sensors, the sensors and controller operable to detect the fault (see par. 0029); an actuator (a actuation mechanism of the switching 12, see par. 0027) coupled to a switch (12), the actuator being operable in the presence of a fault to open the switch to clear the fault; a first pulse tester (a triggered vacuum gap 42, 36) coupled to the power network, the first pulse tester being operable to perform a pulse test of the power network for a predetermined duration of time to determine if the fault is still present (see par. 0039, and 0045, 0046); the actuator being configured to prevent a reclosing of the switch (12) where the first pulse test indicates that the fault is still present (see step 156, par. 0048); and the actuator being further configured to provide the reclosing operation where the first pulse test indicates that the fault is not present (see par. 0047). Regarding claim 15, Djogo discloses the pulse tester (42, 36) being configured to perform subsequent pulse tests (generates a number of testing pulses, see par. 0039, and 0048) if the first pulse test indicates the fault being present, wherein the actuator is further configured to prevent a reclosing of the switch where the subsequent pulse test indicates that the fault is still present (see par. 0048); and the actuator being further configured to provide the reclosing operation where the subsequent pulse test indicates that the fault is not present (see par. 0047). Regarding claim 20, Djogo discloses wherein the power network (10, see figure 1, and par. 0025) is a high-voltage transmission power network. Conclusion 3. Any inquiry concerning this communication or earlier communications from the examiner should be directed to DANNY NGUYEN whose telephone number is (571)272-2054. The examiner can normally be reached M-F 8:00AM-4:30PM. Examiner interviews are available via telephone, in-person, and video conferencing using a USPTO supplied web-based collaboration tool. To schedule an interview, applicant is encouraged to use the USPTO Automated Interview Request (AIR) at http://www.uspto.gov/interviewpractice. If attempts to reach the examiner by telephone are unsuccessful, the examiner’s supervisor, Jared Fureman can be reached on 571-272-2391. The fax phone number for the organization where this application or proceeding is assigned is 571-273-8300. Information regarding the status of published or unpublished applications may be obtained from Patent Center. Unpublished application information in Patent Center is available to registered users. To file and manage patent submissions in Patent Center, visit: https://patentcenter.uspto.gov. Visit https://www.uspto.gov/patents/apply/patent-center for more information about Patent Center and https://www.uspto.gov/patents/docx for information about filing in DOCX format. For additional questions, contact the Electronic Business Center (EBC) at 866-217-9197 (toll-free). If you would like assistance from a USPTO Customer Service Representative, call 800-786-9199 (IN USA OR CANADA) or 571-272-1000. /DANNY NGUYEN/ Primary Examiner, Art Unit 2836
Read full office action

Prosecution Timeline

Jun 30, 2022
Application Filed
Mar 18, 2024
Non-Final Rejection — §102
Sep 27, 2024
Response after Non-Final Action
Nov 21, 2024
Response after Non-Final Action

Precedent Cases

Applications granted by this same examiner with similar technology

Patent 12598729
ELECTROSTATIC DISCHARGE PROTECTION DEVICE AND METHOD THEREOF
2y 5m to grant Granted Apr 07, 2026
Patent 12592559
FIELD DEVICE CURRENT LIMITING
2y 5m to grant Granted Mar 31, 2026
Patent 12587004
LEAKAGE CURRENT PROTECTION DEVICE AND ELECTRICAL APPLIANCES EMPLOYING THE SAME
2y 5m to grant Granted Mar 24, 2026
Patent 12567548
ACCELERATED MOTION RELAY
2y 5m to grant Granted Mar 03, 2026
Patent 12562559
ARC FLASH MITIGATION DEVICE
2y 5m to grant Granted Feb 24, 2026
Study what changed to get past this examiner. Based on 5 most recent grants.

AI Strategy Recommendation

Get an AI-powered prosecution strategy using examiner precedents, rejection analysis, and claim mapping.
Powered by AI — typically takes 5-10 seconds

Prosecution Projections

1-2
Expected OA Rounds
90%
Grant Probability
96%
With Interview (+6.4%)
2y 6m
Median Time to Grant
Low
PTA Risk
Based on 1340 resolved cases by this examiner. Grant probability derived from career allow rate.

Sign in for Full Analysis

Enter your email to receive a magic link. No password needed.

Free tier: 3 strategy analyses per month