Prosecution Insights
Last updated: July 17, 2026
Application No. 19/072,422

POWER DISTRIBUTION UNIT

Non-Final OA §103
Filed
Mar 06, 2025
Priority
Mar 08, 2024 — provisional 63/562,759 +1 more
Examiner
FIN, MICHAEL RUTLAND
Art Unit
2836
Tech Center
2800 — Semiconductors & Electrical Systems
Assignee
MILWAUKEE ELECTRIC TOOL Corporation
OA Round
1 (Non-Final)
80%
Grant Probability
Favorable
1-2
OA Rounds
1y 0m
Est. Remaining
94%
With Interview

Examiner Intelligence

Grants 80% — above average
80%
Career Allowance Rate
513 granted / 640 resolved
+12.2% vs TC avg
Moderate +14% lift
Without
With
+13.6%
Interview Lift
resolved cases with interview
Typical timeline
2y 4m
Avg Prosecution
29 currently pending
Career history
659
Total Applications
across all art units

Statute-Specific Performance

§103
86.4%
+46.4% vs TC avg
§102
8.9%
-31.1% vs TC avg
§112
3.5%
-36.5% vs TC avg
Black line = Tech Center average estimate • Based on career data from 640 resolved cases

Office Action

§103
Notice of Pre-AIA or AIA Status The present application, filed on or after March 16, 2013, is being examined under the first inventor to file provisions of the AIA . Claim Rejections - 35 USC § 103 The following is a quotation of 35 U.S.C. 103 which forms the basis for all obviousness rejections set forth in this Office action: A patent for a claimed invention may not be obtained, notwithstanding that the claimed invention is not identically disclosed as set forth in section 102, if the differences between the claimed invention and the prior art are such that the claimed invention as a whole would have been obvious before the effective filing date of the claimed invention to a person having ordinary skill in the art to which the claimed invention pertains. Patentability shall not be negated by the manner in which the invention was made. Claims 1-4, 6-14, and 16-20 are rejected under 35 U.S.C. 103 as being unpatentable over Gregory, II (US 12,476,472) in view of Sorenson (US 11,271,399). With respect to claims 1, 9, 11 and 19 Gregory teaches a power distribution unit comprising (Fig. 1-2 and 4): a plurality of outlets (108); and a controller (102) configured to: poll the plurality of outlets to determine a polled electrical load of each outlet (col. 9 lines 10-20), add one or more outlets (col. 8 lines 10-25) of the plurality of outlets to a queue (see sequence) based on a comparison of the polled electrical loads and a user set threshold (col. 3 lines 40-50), connect the queued outlets (run programmed sequence) to a power input. Gregory however does not teach monitoring a total electrical load of the power distribution unit, and disconnect, in response to determining that the total electrical load exceeds the user set threshold, one or more outlets of the plurality of outlets from the power input. Sorenson teaches (col. 10 lines 5-25 for example) monitoring a total electrical load of the power distribution unit, and disconnect, in response to determining that the total electrical load exceeds the user set threshold, one or more outlets of the plurality of outlets from the power input (col. 2 lines 15-30). It would have been obvious to one of ordinary skill in the art at the time of the invention to modify Gregory to include the known use of disconnecting a load for the benefit of protecting the system (col. 4 lines 35-40). With respect to claims 2 and 12 Gregory teaches to poll the plurality of outlets, the controller is configured to: connect a first pair of outlets (first group of outlets in sequence) of the plurality of outlets to the power input; and disconnect the first pair of outlets (see moving to next group of outlets in the sequence, col. 8 lines 50-65) of the plurality of outlets from the power input. With respect to claims 3 and 13 Gregory teaches (col. 4 lines 20-50) the ordering the charging sequence by programming the routine however does not teach the assigning a priority. Sorenson teaches (col. 6 lines 40-60) the assigning of priority values. It would have been obvious to one of ordinary skill in the art at the time of the invention to modify Gregory to use a priority ordering of the sequencing for the benefit of ensuring critical loads are charged first to maintain critical operations. With respect to claims 4 and 14 Gregory teaches the power distribution unit however does not teach the determining whether connecting the first outlet to the power input will cause the total electrical load of the power distribution unit to exceed the user set threshold; and add, in response to determining that connecting the first outlet to the power input will not cause the total electrical load of the power distribution unit to exceed the user set threshold, the first outlet to the queue. Sorenson teaches (col. 12 lines 45-55) the using expected power usage or current consumption levels for predicting power draw by the device. It would have been obvious to one of ordinary skill in the art at the time of the invention to apply the expected power levels of Sorenson to unit of Gregory for the benefit of preventing a adding a load to a sequence exceeding the threshold and protecting the system from damage. With respect to claims 6 and 16 Gregory teaches the power distribution however does no teach the disconnection in reverse order. Sorenson teaches the controller is configured to disconnect outlets from the power input in reverse priority order in response to determining that the total electrical load exceeds the user set threshold (col. 10 lines 20-50). It would have been obvious to one of ordinary skill in the art at the time of the invention to modify Gregory to include the disconnecting in reverse priority order to maintain supply to critical operations. With respect to claims 7 and 17 Gregory teaches the power distribution unit however does not teach the determining whether connecting the first outlet to the power input will cause the total electrical load of the power distribution unit to exceed the user set threshold; and add, in response to determining that connecting the first outlet to the power input will not cause the total electrical load of the power distribution unit to exceed the user set threshold, the first outlet to the queue. Gregory further teaches a timer (see configure time or schedule col. 2 lines 45-60); and connect, in response to the timer elapsing, the additional outlets to the power input. Sorenson teaches (col. 12 lines 45-55) the using expected power usage or current consumption levels for predicting power draw by the device. It would have been obvious to one of ordinary skill in the art at the time of the invention to apply the expected power levels of Sorenson to unit of Gregory for the benefit of preventing a adding a load to a sequence exceeding the threshold and protecting the system from damage. With respect to claims 8 and 18 Gregory teaches a plurality of switches (col. 5 line 8), each switch of the plurality of switches being associated with a respective outlet of the plurality of outlets (108); a plurality of outlet sensors (204), each outlet sensor of the plurality of sensors being associated (see Fig. 2) with a respective outlet of the plurality of outlets and configured to sense an electrical load (current draw) of the respective outlet; and wherein the controller is configured to: actuate each switch (see connect each sequence group to power) of the plurality of switches to connect or disconnect the respective outlet, determine an electrical load of each outlet by monitoring a respective outlet sensor. Gregory teaches the use of GFCI setting the maximum current level however Gregory as modified above however does not teach the connection of a main sensor in sensing the total electrical current. It is well known to use main sensor to sense total current of which the Examiner takes Official Notice. It would have been obvious to one of ordinary skill in the art at the time of the invention to further modify Gregory to include the known use of a main sensor for the benefit of rapid determination of an overcurrent condition. With respect to claims 10 and 20 Gregory teaches the polled values are current values. Sorenson teaches electrical loads and the total electrical load are power values (see power draw levels, col. 3 lines 35-40). It would have been obvious to one of ordinary skill in the art at the time of the invention to modify Gregory to use the known alternative of power levels for protecting the system from damage. Allowable Subject Matter Claims 5 and 15 are objected to as being dependent upon a rejected base claim, but would be allowable if rewritten in independent form including all of the limitations of the base claim and any intervening claims. The following is a statement of reasons for the indication of allowable subject matter: With respect to claims 5 and 15 Gregory as modified above teaches power distribution unit however does not teach the further limitation each outlet of the plurality of outlets is assigned a priority; and to add one or more outlets of the plurality of outlets to the queue, the controller is configured to: select a second outlet of the plurality of outlets, the second outlet having a lower priority than the first outlet, determine whether connecting the second outlet and any queued outlets to the power input will cause the total electrical load of the power distribution unit to exceed the user set threshold; and add, in response to determining that connecting the second outlet and any queued outlets to the power input will not cause the total electrical load of the power distribution unit to exceed the user set threshold, the second outlet to the queue. At least this further limitation is not taught or rendered obvious by the prior art of record. Conclusion Any inquiry concerning this communication or earlier communications from the examiner should be directed to Michael Fin whose telephone number is (571)272-5921. The examiner can normally be reached Monday-Friday 9am-5:30. Examiner interviews are available via telephone, in-person, and video conferencing using a USPTO supplied web-based collaboration tool. To schedule an interview, applicant is encouraged to use the USPTO Automated Interview Request (AIR) at http://www.uspto.gov/interviewpractice. If attempts to reach the examiner by telephone are unsuccessful, the examiner’s supervisor, Rexford Barnie can be reached at 571-272-7429. The fax phone number for the organization where this application or proceeding is assigned is 571-273-8300. Information regarding the status of published or unpublished applications may be obtained from Patent Center. Unpublished application information in Patent Center is available to registered users. To file and manage patent submissions in Patent Center, visit: https://patentcenter.uspto.gov. Visit https://www.uspto.gov/patents/apply/patent-center for more information about Patent Center and https://www.uspto.gov/patents/docx for information about filing in DOCX format. For additional questions, contact the Electronic Business Center (EBC) at 866-217-9197 (toll-free). If you would like assistance from a USPTO Customer Service Representative, call 800-786-9199 (IN USA OR CANADA) or 571-272-1000. MICHAEL FIN Primary Examiner Art Unit 2836 /MICHAEL R. FIN/Primary Examiner, Art Unit 2836
Read full office action

Prosecution Timeline

Mar 06, 2025
Application Filed
Apr 28, 2026
Non-Final Rejection mailed — §103 (current)

Precedent Cases

Applications granted by this same examiner with similar technology

Patent 12683424
CHARGER FOR A BATTERY PACK, CHARGING SYSTEM AND METHOD OF CHARGING
2y 11m to grant Granted Jul 14, 2026
Patent 12676513
POWER TRANSFER DISABLEMENT SWITCH IN A WIRELESS POWER RECEPTION APPARATUS
2y 10m to grant Granted Jul 07, 2026
Patent 12676470
OVER VOLTAGE PROTECTION FOR A WIRELESS POWER TRANSFER SYSTEM
1y 10m to grant Granted Jul 07, 2026
Patent 12676498
BACKUP POWER SUPPLY
1y 9m to grant Granted Jul 07, 2026
Patent 12676474
POWER SUPPLY CIRCUIT, BACKUP POWER SUPPLY SYSTEM, AND MOVING VEHICLE
1y 5m to grant Granted Jul 07, 2026
Study what changed to get past this examiner. Based on 5 most recent grants.

Strategy Recommendation AI-generated — please review before filing

Get a prosecution strategy drawn from examiner precedents, rejection analysis, and claim mapping.
Typically takes 5-10 seconds — AI-generated, attorney review required before filing

Prosecution Projections

1-2
Expected OA Rounds
80%
Grant Probability
94%
With Interview (+13.6%)
2y 4m (~1y 0m remaining)
Median Time to Grant
Low
PTA Risk
Based on 640 resolved cases by this examiner. Grant probability derived from career allowance rate.

Sign in with your work email

Enter your email to receive a magic link. No password needed.

Personal email addresses (Gmail, Yahoo, etc.) are not accepted.

Free tier: 3 strategy analyses per month